Series 'FT' Flash Tanks

COLTON flash tanks offer a unique inlet baffle arrangement designed to enhance flash separation and extend tank life.

All steam systems produce flash steam which is usually wasted when it escapes through the condensate receiver vent pipe. The COLTON flash tank allows you to use this waste energy by capturing the flash steam and using it elsewhere in your system.

Flash steam is exactly the same as live steam and is every bit as useful. Flash steam should be regarded as a free source of low pressure steam in any system that operates with more than one steam pressure.

Ordering Information Required:
  • Pressure at high pressure steam trap/s or blow down metering valve/s feeding the flash tank.
  • Volume of high pressure condensate (usually expressed in lbs/hr.)
  • Pressure of the lower pressure system that we will be supplementing.
Sample Options:
  • Steam trap and strainer
  • Pressure gage, syphon and pet cock
  • Safety valve
  • Drip pan elbow
  • Back pressure regulator
  • Pressure reducing valve
Unit of Measure

Specifications

A

N/A 6 in

B

N/A 47 in

C

N/A 38 in

D

N/A 13 in

E

N/A 8.00 in

F

N/A 9 in

G

N/A 25 1/2 in

H

N/A 2.50 in

J

N/A 3/4 in

K

N/A 8.8 in

L

N/A 1 1/2 in

M

N/A 2 1/2 in

Weight

N/A 75 lb

Design Standards

N/A ANSI B16.5

Design Code

N/A ASME Section VIII, Div. 1, latest revision

Design Pressure

N/A 285 psig

Design Temperature

N/A 100 ºF

M.D.M.T.

N/A -20 ºF

Hydrostatic Test

N/A 430 psig

Design Steam Pressure

N/A 150 psig saturated

Heat Treatments

N/A None

Service

N/A Non-Lethal

Material of Construction

N/A Carbon Steel per ASME Sect. II (A)

Information Required for Sizing

N/A

  • Pressure at high pressure steam trap inlet (or blowdown metering valve inlet)
  • Flash steam system pressure
  • Amount of high pressure condensate