CVB-200 Series - PRODUCT DATA BULLETIN
 CVB-200 Series - INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Model 'CVB-200'

Available in brass or stainless steel bodies with 1/2" npt end connections for steam pressures up to 200 psig saturated steam service.

Materials of Construction:
Body: Brass or Stainless Steel
Cover: Brass or Stainless Steel
Gasket: Stainless Steel
Ball: Stainless Steel
Seat: Stainless Steel

Operation:
The preferred method of installation is in the vertical upright position. A horizontal installation should only be used if no other option is available, and only above the condensate level.

Vacuum breakers should be placed at the highest practical point for the system or equipment being serviced.

Unit of Measure
Items
Vacuum Breaker CVB-200

Vacuum Breaker CVB-200

Vacuum Breaker CVB-200

Vacuum Breaker CVB-200
Maximum Differential Pressure PMA N/A 230 psi N/A 580 psi
Maximum Operating Pressure PMO N/A 200 psi
Maximum Operating Temperature TMO N/A 400 ºF N/A 500 ºF
Body Material N/A Brass N/A 304 Stainless Steel
Gasket Material N/A 304 Stainless Steel
Cover Material N/A Brass N/A 304 Stainless Steel
Ball Material N/A 304 Stainless Steel
Seat Material N/A 304 Stainless Steel
Air Capacity 1" Hg N/A 1.5 ft³/min
Air Capacity 2" Hg N/A 2.0 ft³/min
Air Capacity 3" Hg N/A 2.5 ft³/min
Air Capacity 4" Hg N/A 2.75 ft³/min
Air Capacity 5" Hg N/A 2.95 ft³/min
Air Capacity 6" Hg N/A 3.15 ft³/min
Air Capacity 7" Hg N/A 3.5 ft³/min
Air Capacity 8" Hg N/A 3.8 ft³/min
Air Capacity 10" Hg N/A 4.2 ft³/min
Air Capacity 12" Hg N/A 4.6 ft³/min
Air Capacity 15" Hg N/A 5.0 ft³/min